The toxicity of lead mainly affects the nervous system. Long-term lead exposure will cause severe damage to the brain and kidneys of the exposed person.

The Ministry of Labor recently revised and announced the "Lead Poisoning Prevention Rules". The main revision of this law is that new local exhaust devices should be designed by trained and qualified professionals, and a design report and an original performance test report should be produced; in addition, Clearly define the qualifications, training courses, hours, etc. of design professionals to enhance the design capabilities of personnel and the performance of equipment. (Amended Article 31, Article 31-1) (Effective from July 1, 2025).

Corrected release date: June 13, 2024

Some of the revised provisions came into effect on July 1, 2025. (Article 26, paragraph 2, Article 31, paragraphs 2 to 5, and Article 31-1)

 

The key provisions are as follows:

 

Article 26

The internal structure of the duct of the local exhaust device installed by the employer should be easy to clean and measure, and cleaning ports and measuring holes should be provided at appropriate locations.

The local exhaust device installed by the employer in accordance with the provisions of Paragraph 2 of Article 31 shall be installed at the appropriate location of the gas hood connecting duct to monitor the static pressure, flow rate or other devices sufficient to indicate the normal operation of the equipment.

 

Article 31

If the employer installs closed equipment, local exhaust devices or overall ventilation devices, they should be properly designed by professionals and maintain their effective performance.

When installing local exhaust devices, the employer shall assign or entrust professionals who have been trained and qualified by the central competent authority to design and prepare a local exhaust device design report.

After the installation of the local exhaust device in the preceding paragraph is completed, an original performance test shall be carried out and an original performance test report shall be prepared based on the test results; the relevant documents and records shall be kept for ten years.

If the local exhaust device installed by the employer is a chemical exhaust cabinet type, it is not subject to the restrictions of the previous two paragraphs.

When modifying the local exhaust device installed by the employer in accordance with the provisions of Paragraph 2, the employer shall comply with the provisions of Paragraphs 2 and 3. However, this does not apply to those that have no significant impact on its performance.

 

Article 31-1

The qualifications, training courses and hours, training units, local exhaust device design report and original performance test report that professionals engaged in local exhaust device design should have as specified in the second and third paragraphs of the previous article shall apply mutatis mutandis. The provisions of Article 38 and Article 38-1 of the Chemical Substance Hazard Prevention Standards.

 

Article 34

When employers engage workers in lead work, they should set up a rest room outside the workplace that meets the following requirements:

1. The entrance and exit of the break room should be equipped with flushing water pipes or fully moistened mats to remove lead dust attached to workers' feet, and a brush or vacuum dust collector for removing lead dust should be installed at the entrance.

2. The floor structure of the rest room should be easy to use a vacuum dust collector or clean with water.

 

Article 36

To prevent lead dust contamination from lead, lead mixtures or sinter mixtures, employers should flush the workplace, restrooms, restaurants, etc. with water or use a vacuum dust collector or appropriate solution at least once a day. However, this does not apply to cases where there is no risk of lead dust pollution.

 

Article 37

When employers have workers engage in lead work, they should prepare toilet facilities such as nail brushes, soap or appropriate solutions for hand washing and mouth washing at the workplace for workers to wash themselves to avoid lead dust contamination.

 

Article 45

The respiratory protective equipment and protective clothing specified in Paragraphs 1 and 2 should be equipped with special storage equipment and kept separately from other clothing after use, and are prohibited from being brought into places other than lead workplaces.

 

 